AUMA SA 07.2 Operation Instructions Manual page 52

Multi-turn actuator; control unit: electromechanic with actuator controls
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

Corrective action
Table 11:
Faults and warnings via status indications in the display
Indication on display
Warnings S0005
Not ready REMOTE S0006
Fault S0007
Out of specification S0008
Function check S0009
Maintenance required S0010
Failure S0011
Table 12:
Warnings and Out of specification
Indication on display
Config. warning
Internal warning
24 V DC external
Wrn on time running
Wrn on time starts
Failure behav. active
Wrn input AIN 1
Wrn input AIN 2
Wrn setpoint position
52
SA 07.2
SA 16.2/SAR 07.2
Description/cause
Collective signal 02:
Indicates the number of active warnings.
Collective signal 04:
Indicates the number of active signals.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
Collective signal 07:
Indication according to NAMUR recommenda-
tion NE 107
Actuator is operated outside the normal ope-
ration conditions.
Collective signal 08:
Indication according to NAMUR recommenda-
tion NE 107
The actuator is being worked on; output si-
gnals are temporarily invalid.
Collective signal 09:
Indication according to NAMUR recommenda-
tion NE 107
Recommendation to perform maintenance.
Collective signal 10:
Indication according to NAMUR recommenda-
tion NE 107
Actuator function failure, output signals are
invalid
Description/cause
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restricti-
ons.
Collective signal 15:
Device warnings
The device can still be operated with restricti-
ons.
The external 24 V DC voltage supply of the
controls has exceeded the power supply limits.
Warning on time max. running time/h excee-
ded
Warning on time max. number of motor starts
(starts) exceeded
The failure behaviour is active since all requi-
red setpoints and actual values are incorrect.
Warning: Loss of signal analogue input 1
Warning: Loss of signal analogue input 2
Warning: Loss of signal of actuator setpoint
position
Possible causes:
Input signal for setpoint = 0 (signal loss)
SAR 16.2 Control unit: electromechanic
AC 01.2 Intrusive
For indicated value > 0:
Details.
Press push button
For details, refer to <Warnings and Out of
specification> table.
Press push button
Details.
For details, refer to <Not ready REMOTE and
Function check> table.
Press push button
Details to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Press push button
Details.
For details refer to <Warnings and Out of
specification> table.
Press push button
Details.
For details, refer to <Not ready REMOTE and
Function check> table.
Press push button
Details to display a list
of detailed indications.
Press push button
Details to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Remedy
Press push button
Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Press push button
Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Check 24 V DC voltage supply.
Check modulating behaviour of actuator.
Check parameter Perm. running time/h
M0356, re-set if required.
Check modulating behaviour of actuator.
Check parameter Permissible starts/h
M0357, re-set if required.
Verify signals:
Setpoint E1
Actual value E2
Actual process value E4
Check wiring.
Check wiring.
Check setpoint signal.