f. Slide the module out of the chassis and place the module on an antistatic
surface.
2. Load the chassis onto a mechanical lift or floor jack as follows:
a. Position the mechanical lift next to the shipping pallet that holds the
chassis.
b. Elevate the lift platform to the level of the bottom of the chassis (or no
more than 1/4 inch [0.635 cm] below the bottom of the chassis).
c. Use two persons to slide the chassis fully onto the lift so that the side of
the chassis touches or is close to the vertical rails on the lift. Make sure
that the front and rear of the chassis are unobstructed so you can easily
push the chassis into the rack.
Note: To prevent personal injury or damage to the chassis, never attempt to
lift or tilt the chassis using the handles on modules (such as power supplies,
fans, or cards); these types of handles are not designed to support the weight
of the unit.
CAUTION:
To lift the chassis, use a mechanical lift. Do not use the handles on the side
of the chassis (the handles are not rated for lifting over 200 pounds [91 kg]).
Use the side handles for only repositioning the chassis after it is already on
the mechanical lift or in the rack or cabinet.
3. Use the mechanical lift to move and align the rear of the chassis to the front
of the rack or cabinet. Make sure that the bottom of the chassis is elevated to
the height of the bottom-support rails or no more than 1/4 inch (0.6 cm)
above the rails.
Note: The IBM c-type SAN Device has the front-to-back cold-aisle and
hot-aisle air flow design. We recommend that you maintain a minimum air
space of 7 inches (30.5 cm) at the chassis front and back air vents.
4. Push the chassis halfway onto the rack or cabinet.
Use two persons to push the chassis onto the bottom-support rails. Push the
lower half of the front side of the chassis so that the back side enters the rack
first, and push until the chassis is halfway onto the rack. See Figure 31 on
page 66. Ensure that the chassis does not get caught on any of the expansion
edges of the bottom-support rail.
Chapter 3. Installing the IBM c-type SAN Device
65