Code
(hex)
Fault / Aux. code
0002
0003
0004
0005...0008
0009
000A
000B
000C
000D
000E...0010
0011
Cause
Maximum speed limit
Check settings of parameters
or calculated field
30.11 Minimum speed
weakening point too
30.12 Maximum speed
low.
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal speed.
Make sure that
30.12 > (0.55 × 99.09) >
(0.50 × synchronous speed)
30.11 < 0, and
supply voltage > (0.66 × 99.07).
Maximum torque limit
Check settings of parameter 99.12
too low.
Motor nominal torque, and the torque
limits in group 30 Limits.
Make sure that the maximum torque
limit in force is greater than 100%.
Current measurement
Contact your local ABB
calibration did not finish
representative.
within reasonable time
Internal error.
Contact your local ABB
representative.
(Asynchronous motors
Contact your local ABB
only)
representative.
Acceleration did not
finish within reasonable
time.
(Asynchronous motors
Contact your local ABB
only)
representative.
Deceleration did not
finish within reasonable
time.
(Asynchronous motors
Contact your local ABB
only)
representative.
Speed dropped to zero
during ID run.
(Permanent magnet
Contact your local ABB
motors only)
representative.
First acceleration did
not finish within
reasonable time.
(Permanent magnet
Contact your local ABB
motors only)
representative.
Second acceleration
did not finish within
reasonable time.
Internal error.
Contact your local ABB
representative.
(Synchronous
Contact your local ABB
reluctance motors only)
representative.
Pulse test error.
79