ABB ACH580 Series Installation, Operation And Maintenance Manual page 124

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

124
Fault
Code
3006
3008
3009
3010
3011
3012
ACH580 E-Clipse Bypass
Fault Name In
Panel
UNDERVOLTAGE
Fault will be generated
only if the drive is
controlling the motor
and the power to the
bypass is removed
before the drive shuts
down. This fault is
generated when the
drive contactor opens
while the drive is
operating.
DRIVE AI2 LOSS
Only displayed when in
Supervisory mode.
Indicates that AI2 on the
drive has failed.
MTR OVERLOAD
Bypass opens on motor
overload conditions
defined in the drive
INP PHASE A LOSS Fault will be generated
when the bypass
contactor is requested to
be closed and the RBCU
does not sense voltage
on Phase A
INP PHASE B LOSS Fault will be generated
when the bypass
contactor is requested to
be closed and the RBCU
does not sense voltage
on Phase B
INP PHASE C LOSS Fault will be generated
when the bypass
contactor is requested to
be closed and the RBCU
does not sense voltage
on Phase C
ACH580 Installation, Operation and Maintenance Manual
Fault
Possible Cause
Loose J7 connector on
RBCU unit (refer to
page
99
connector location)
Loose input wiring
Incoming power
problems
Check connections on
drive
Drive Mode:
Bad Motor
Bad CTs
Bad RBCU
Bypass mode:
Bad motor
Bad CTs
Bad RBCU
Either mode:
low input voltage
Loose J7 connector
(refer to page
J7 connector location)
Loose wiring on
Contactor assembly.
Blown upstream fuse
Loose J7 connector
(refer to page
J7 connector location)
Loose wiring on
Contactor assembly.
Blown upstream fuse
Loose J7 connector
(refer to page
J7 connector location)
Loose wiring on
Contactor assembly.
Blown upstream fuse
Corrective Action
Check that J7 connector
is firmly seated in RBCU
for the J7
(refer to page
J7 connector location)
Check tightness of
incoming connections
Check Parameter 0413
to view voltage level at
time of trip
Check upstream
protection
Check connections on
drive
Check if overload
condition exists
Drive Mode:
Refer to ACH580
manual for proper
troubleshooting
techniques
Bypass Mode:
Check that J2 connector
is firmly seated in RBCU
(refer to page
J7 connector location)
Use clam
p meter to verify mtr
current vs. display in
parameter 0101
Check input voltage
Check J7 connector
99
for the
(refer to page
J7 connector location)
Check yellow wire on
input block
Check incoming voltage,
phase to ground
Check J7 connector
99
for the
(refer to page
J7 connector location)
Check black wire on
input block
Check incoming voltage,
phase to ground
Check J7 connector
99
for the
(refer to page
J7 connector location)
Check red on input block
Check incoming voltage,
phase to ground
99
for the
99
for the
99
for the
99
for the
99
for the