ABB ACH580 Series Installation, Operation And Maintenance Manual page 64

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

64
Code
(hex)
A8A0
A8A1
A8A2
A8B0
A8B1
A8B2
A8B3
A8B4
ACH580-01 Installation
Warning / Aux. code
AI supervision
Programmable warning:
12.03 AI supervision
function
RO life warning
0001
0002
0003
RO toggle warning
0001
0002
0003
ABB Signal supervision 1
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
ABB Signal supervision 2
(Editable message text)
Programmable warning:
32.16 Supervision 2 action
ABB Signal supervision 3
(Editable message text)
Programmable warning:
32.26 Supervision 3 action
ABB Signal supervision 4
(Editable message text)
Programmable warning:
32.36 Supervision 4 action
ABB Signal supervision 5
(Editable message text)
Programmable warning:
32.46 Supervision 5 action
ACH580 Installation, Operation and Maintenance Manual
Cause
An analog signal is
Check signal level at the analog input.
outside the limits
Check the wiring connected to the
specified for the analog
input.
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard AI.
The relay has changed
Change the control board or stop
states more than the
using the relay output.
recommended number
of times.
Relay output 1
Change the control board or stop
using relay output 1.
Relay output 2
Change the control board or stop
using relay output 2.
Relay output 3
Change the control board or stop
using relay output 3.
The relay output is
Replace the signal connected to the
changing states faster
relay output source with a less
than recommended,
frequently changing signal.
eg. if a fast changing
frequency signal is
connected to it. The
relay lifetime will be
exceeded shortly.
Relay output 1
Select a different signal with
parameter 10.24 RO1 source.
Relay output 2
Select a different signal with
parameter 10.27 RO2 source.
Relay output 3
Select a different signal with
parameter 10.30 RO3 source.
Warning generated by
Check the source of the warning
the signal supervision
(parameter 32.07 Supervision 1
function 1.
signal).
Warning generated by
Check the source of the warning
the signal supervision
(parameter 32.17 Supervision 2
function 2.
signal).
Warning generated by
Check the source of the warning
the signal supervision
(parameter 32.27 Supervision 3
function 3.
signal).
Warning generated by
Check the source of the warning
the signal supervision
(parameter 32.37 Supervision 4
function 4.
signal).
Warning generated by
Check the source of the warning
the signal supervision
(parameter 32.47 Supervision 5
function 5.
signal).
What to do