ACH580 Installation, Operation and Maintenance Manual
Code
(hex)
AFEF
AFF0
AFF1
AFF5
AFF6
AFF8
AFFE
B5A0
D501
D502
D503
Warning / Aux. code
Start interlock 2
Start interlock 3
Start interlock 4
Override new start
required
Identification run
Motor heating active
Override active
STO event
Programmable event:
31.22 STO indication run/
stop
No more available PFC
motors
All motors interlocked
VSD controlled PFC motor
interlocked
Cause
Start interlock 2 is
Check the signal source selected for
keeping the drive from
parameter 20.42 Start interlock 2.
starting.
Start interlock 3 is
Check the signal source selected for
keeping the drive from
parameter 20.43 Start interlock 3.
starting.
Start interlock 4 is
Check the signal source selected for
keeping the drive from
parameter 20.44 Start interlock 4.
starting.
The Safe torque off
A new start signal is required to start
function was active and
the drive again.
has been reset while in
Override.
Motor ID run will occur
Informative warning.
at next start.
Pre-heating is being
Informative warning.
performed
Motor pre-heating is active. Current
specified by parameter 21.16 Pre-
heating current is being passed
through the motor.
Drive is in override
Informative warning.
mode.
Safe torque off function
Informative warning.
is active, ie. safety
Check safety circuit connections. For
circuit signal(s)
more information, see chapter The
connected to connector
Safe torque off function in the
STO is lost.
Hardware manual of the drive and
parameter 31.22 STO indication run/
stop.
No more PFC motors
Check that there are no interlocked
can be started because
PFC motors, see parameters:
they can be interlocked
76.81...76.84.
or in the Hand mode.
If all motors are in use, the PFC
system is not adequately dimensioned
to handle the demand.
All the motors in the
Check that there are no interlocked
PFC system are
PFC motors, see parameters
interlocked.
76.81...76.84.
The motor connected
Motor connected to the drive is
to the drive is
interlocked and thus cannot be
interlocked
started.
(unavailable).
Remove the corresponding interlock
to start the drive controlled PFC
motor. See parameters 76.81...76.84.