ABB ACH580 Series Installation, Operation And Maintenance Manual page 144

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

144
575 Volt
Output Range
1, 2
Type Code
A
ACH580-PxR-02A7-6
2.7
ACH580-PxR-03A9-6
3.9
ACH580-PxR-06A1-6
6.1
ACH580-PxR-09A0-6
9
ACH580-PxR-011A-6
11
ACH580-PxR-017A-6
17
ACH580-PxR-022A-6
22
ACH580-PxR-027A-6
27
ACH580-PxR-032A-6
32
ACH580-PxR-041A-6
41
3
ACH580-PxR-052A-6
52
ACH580-PxR-062A-6
62
ACH580-PxR-077A-6
77
ACH580-PxR-099A-6
99
ACH580-PxR-125A-6
125
ACH580-PxR-144A-6
144
1) "PxR" represents both PCR and PDR.
2) PCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) PCR supports Delta network configuration.
ACH580-PCR/PDR
Base
Circuit
Drive
Breaker
Circuit
Frame
UL
Breaker UL
HP
Size
(NEMA)
(NEMA)
Type 1
Type 3R
and 12
#10
2
R2
62 in-lbs
62 in-lbs
#12
3
R2
62 in-lbs
62 in-lbs
5
R2
#10
7.5
R2
62 in-lbs
62 in-lbs
10
R2
15
R2
#6
62 in-lbs
62 in-lbs
20
R3
25
R3
#4
62 in-lbs
62 in-lbs
30
R3
#3
40
R5
62 in-lbs
#2
50
R5
62 in-lbs
#1
60
R6
62 in-lbs
#1/0
Consult
75
R6
62 in-lbs
Factory
#3/0
100
R7
124 in-lbs
125
R7
250 MCM
124 in-lbs
150
R8
ACH580 Installation, Operation and Maintenance Manual
Maximum Power Wiring Data
Disconnect
Disconnect
Switch UL
Switch
(NEMA) Type
UL (NEMA)
1 and 12
Type 3R
#10
#12
#10
#10
55 in-lbs
55 in-lbs
#10
#6
#6
#6
55 in-lbs
55 in-lbs
#4
#4
#4
55 in-lbs
55 in-lbs
#3
55 in-lbs
#2
55 in-lbs
#1
275 in-lbs
#1/0
Consult
275 in-lbs
Factory
#3/0
275 in-lbs
250 MCM
275 in-lbs
300 MCM
275 in-lbs
Ground
Ground
ACH580
Lugs
Lugs
Motor
UL (NEMA)
UL (NEMA)
Terminals
Type 1
Type 3R
and 12
#6
1.1 ft-lbs
#2
50 in-lbs
#2
50 in-lbs
#2
2.6 ft-lbs
#2/0
4.1 ft-lbs
300 MCM
22.1 ft-lbs
Consult
Factory
3 x #3/0
500 MCM
250 in-lbs
29.5 ft-lbs
2 x 300
MCM
29.6 ft-lbs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents