ABB ACH580 Series Installation, Operation And Maintenance Manual page 103

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual
Nominal Output
Ratings
Drive
1
Current
Type Code
A
ACH580-BxR-02A7-6
2.7
ACH580-BxR-03A9-6
3.9
ACH580-BxR-06A1-6
6.1
ACH580-BxR-09A0-6
9
ACH580-BxR-011A-6
11
ACH580-BxR-017A-6
17
ACH580-BxR-022A-6
22
ACH580-BxR-027A-6
27
ACH580-BxR-032A-6
32
ACH580-BxR-041A-6
41
3
ACH580-BxR-052A-6
52
ACH580-BxR-062A-6
62
ACH580-BxR-077A-6
77
ACH580-BxR-099A-6
99
ACH580-BxR-125A-6
125
ACH580-BxR-144A-6
144
1)
"BxR" represents both BCR and BDR.
2)
BCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) BCR supports Delta network configuration.
Base
Package
Circuit
Drive
Power
Breaker
Breaker
Frame
UL
Size
(NEMA)
(NEMA)
HP
Type 1
Type 3R
and 12
2
R2
3
R2
#12
5
R2
62 in-lbs
62 in-lbs
7.5
R2
10
R2
15
R2
#10
20
R3
62 in-lbs
62 in-lbs
25
R3
30
R3
#6
62 in-lbs
40
R5
#2
50
R5
62 in-lbs
#1
60
R5
62 in-lbs
#1/0
Consult
75
R5
62 in-lbs
#3/0
100
R7
124 in-lbs
125
R7
250
MCM
124 in-lbs
150
R8
Maximum Wire Size and Terminal Torque
Circuit
Disconnect
Disconnect
Switch
Switch
UL
UL (NEMA)
UL (NEMA)
Type
Type 3R
1 and 12
2
575 Volts
#12
#10
#10
55 in-lbs
55 in-lbs
#6
#6
55 in-lbs
55 in-lbs
#10
#4
#4
55 in-lbs
55 in-lbs
#3
55 in-lbs
#2
55 in-lbs
#1
275 in-lbs
#1/0
Consult
factory
275 in-lbs
factory
#3/0
275 in-lbs
250 MCM
275 in-lbs
300 MCM
275 in-lbs
Ground
Motor
Motor
Lugs
Terminals
Terminals
UL
UL (NEMA)
UL (NEMA)
(NEMA)
Type 1
Type 3R
Type 1
and 2
and 2
#6
#6
#4
11-13 in lbs
11-13 in lbs
35 in-lbs
#1
35 in-lbs
#1
35 in-lbs
#2
50 in-lbs
#2/0
110 in-lbs
Consult
factory
#2/0
3 x #3/0
71 in-lbs
250 in-lbs
300 MCM
301 in-lbs
ACH580 E-Clipse Bypass
103
Ground
Lugs
UL
(NEMA)
Type 3R
#4
35 in-lbs
Consult
factory

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents