ABB ACH580 Series Installation, Operation And Maintenance Manual page 74

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

74
Code
(hex)
65A1
6681
6682
6683
6684
6685
6686
6882
6885
7081
7085
7100
7121
ACH580-01 Installation
Fault / Aux. code
FBA A parameter conflict
EFB comm loss
Programmable fault: 58.14
Communication loss
action
EFB config file
EFB invalid
parameterization
EFB load fault
EFB fault 2
EFB fault 3
Text 32-bit table overflow
Text file overflow
Control panel loss
Programmable fault: 49.05
Communication loss
action
Incompatible option
module
Excitation current
Motor stall
Programmable fault: 31.24
Stall function
ACH580 Installation, Operation and Maintenance Manual
Cause
The drive does not
Check PLC programming.
have a functionality
Check settings of parameter groups
requested by PLC, or
50 Fieldbus adapter (FBA) and 51
requested functionality
FBA A settings.
has not been activated.
Communication break
Check the status of the fieldbus
in embedded fieldbus
master (online/offline/error etc.).
(EFB) communication.
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31
on the control unit.
Embedded fieldbus
Contact your local ABB
(EFB) configuration file
representative.
could not be read.
Embedded fieldbus
Check the settings in parameter group
(EFB) parameter
58 Embedded fieldbus.
settings inconsistent or
not compatible with
selected protocol.
Embedded fieldbus
Contact your local ABB
(EFB) protocol
representative.
firmware could not be
loaded.
Version mismatch
between EFB protocol
firmware and drive
firmware.
Fault reserved for the
Check the documentation of the
EFB protocol
protocol.
application.
Fault reserved for the
Check the documentation of the
EFB protocol
protocol.
application.
Internal fault.
Reset the fault. Contact your local
ABB representative if the fault
persists.
Internal fault.
Reset the fault. Contact your local
ABB representative if the fault
persists.
Control panel or PC
Check PC tool or control panel
tool selected as active
connection.
control location for
Check control panel connector.
drive has ceased
Disconnect and reconnect the control
communicating.
panel.
Fieldbus option module
Replace the module with a supported
not supported.
type.
Excitation current
feedback low or
missing
Motor is operating in
Check motor load and drive ratings.
stall region because of
Check fault function parameters.
e.g. excessive load or
insufficient motor
power.
What to do

Hide quick links: