ABB ACH580 Series Installation, Operation And Maintenance Manual page 127

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual
Fault
Code
3037
3038
3039
3101
3102
3201
3202
3203
3204
3205
3206
Fault Name In
Panel
PCB TEMP
RBCU unit has reached
190 degrees Fahrenheit,
88 degrees Celsius
NO DRIVE DATA
No drive data available
FBA PAR CONF
Non embedded fieldbus
has detected an error in
Group 51 parameters
SFLASH CORRUPT Internal checksum error NA
PMAP FILE
Parameter file is corrupt
T1 OVERLOAD
T1 program cycle is
overloaded
T2 OVERLOAD
T2 program cycle is
overloaded
T3 OVERLOAD
T3 program cycle is
overloaded
STACK OVERFLOW Program cycle is
overloaded
UNKNOWN CB
Bypass control board
type is unknown.
UNKNOWN DRIVE
Drive reports rating not
found in bypass
software
Fault
Possible Cause
Cabinet cooling has
failed
Ambient conditions too
high
Bad RBCU unit
Bypass not able to
extract drive data on
initial power up due to:
Bad cable/connection
between drive and
bypass.
Drive parameter 95.21,
bit 5 not set for
"Bypass present"
Incorrect settings in
Group 51
NA
NA
NA
NA
NA
Drive does not match
drives configured in
bypass RBCU
127
Corrective Action
Stop drive and let cool
down and restart
Add additional cooling
Replace RBCU
Proper seating of cable
in drive and RBCU
(connector J3)
Check that drive
parameter 95.21, bit 5 =
"Bypass present"
Check drive Group 58
Follow DriveLink
recovery procedure then
cycle power to bypass.
Verify Group 51
parameters
Cycle power
Replace RBCU
Upgrade firmware
Cycle Power
Contact ABB with
information that
preceded fault
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
Contact ABB with
information that
proceeded fault
Replace RBCU or
reload with most current
firmware
ACH580 E-Clipse Bypass