ABB ACH580 Series Installation, Operation And Maintenance Manual page 77

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual
Code
(hex)
80A0
80B0
80B1
80B2
80B3
80B4
80B5
9081
9082
Fault / Aux. code
AI supervision
Programmable fault:
12.03 AI supervision
function
0001
0002
0003
0004
Signal supervision 1
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
Signal supervision 4
(Editable message text)
Programmable fault:
32.36 Supervision 4 action
Signal supervision 5
(Editable message text)
Programmable fault:
32.46 Supervision 5 action
Signal supervision 6
(Editable message text)
Programmable fault:
32.56 Supervision 6 action
External fault 1
(Editable message text)
Programmable fault: 31.01
External event 1 source
31.02 External event 1
type
External fault 2
(Editable message text)
Programmable fault: 31.03
External event 2 source
31.04 External event 2
type
Cause
An analog signal is
Check signal level at the analog input.
outside the limits
Check the auxiliary code.
specified for the analog
Check the wiring connected to the
input.
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard AI.
AI1LessMIN
AI1GreaterMAX
AI2LessMIN.
AI2GreaterMAX
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.07 Supervision 1
function 1.
signal).
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.17 Supervision 2
function 2.
signal).
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.27 Supervision 3
function 3.
signal).
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.37 Supervision 4
function 4.
signal).
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.47 Supervision 5
function 5.
signal).
Fault generated by the
Check the source of the fault
signal supervision
(parameter 32.57 Supervision 6
function 6.
signal).
Fault in external device
Check the external device.
1.
Check setting of parameter 31.01
External event 1 source.
Fault in external device
Check the external device.
2.
Check setting of parameter 31.03
External event 2 source.