Display/Switch Setting

Settings for display
BUS
MS
NS
SOL
COM A
Display
MS
Lights on in green: Normal status.
Lights on in red:
Fatal failure occurred.
NS
Lights off:
Offline/Power is OFF.
Blinks in green:
Online/Communication is not established.
Lights on in green: Online/Communication is established.
Blinks in red:
Minor communication error occurred.
Lights on in red:
Fatal communication error occurred.
SOL
Lights on:
Power is supplied to solenoid valves/output at specified
voltage.
Lights off:
Power is not supplied to solenoid valves/output at
specified voltage. ( Voltage dropped to lower than 20V. )
COM A
Lights on:
COM A is receiving data.
Lights off:
COM A has no received data.
COM B
Lights on:
COM B is receiving data.
Lights off:
COM B has no received data.
COM C
Lights on:
COM C is receiving data.
Lights off:
COM C has no received data.
COM D
Lights on:
COM D is receiving data.
Lights off:
COM D has no received data.
NOTE
When connecting manifold valve only without connecting Input unit manifold, LEDs of
COM A - D do not light. To make them light, connect a terminal plug to the unused
connector of SI unit ( "C1" or "0" ).
18
GATEWAY UNIT
EX500 SERIES
COM B
COM C
COM D
Description
Switch setting
Open the station number switch protective cover and set the switches with a
sharp-pointed watchmakers screwdriver etc.
NOTE
1. Be sure to turn off the power before setting the switches.
2. Be sure to set these switches before use.
3. After opening and closing the station number switch protective cover, tighten the
screws by proper tightening torque. ( Tightening torque: 0.6Nm )
0
9
1
8
2
7
3
6
4
5
SW1
Address setting switches
1 and 2 ( SW1 and SW2 )
These switches can set the node address.
SW1
SW2
0
0
9
1
9
1
8
2
8
2
7
3
7
3
6
4
6
4
5
5
10
1
SW1: Sets the second digit.
SW2: Sets the first digit.
The settings of each switch are as shown in the table below:
( The initial settings are: SW1; 6, SW2; 3 and SW3; 0. )
SW1
SW2
Node address
0
0
0
0
1
1
0
2
2
6
3
63
6
4
PGM ( Note )
9
9
Note: When PGM is selected, the node address or data rate will be set via DeviceNet network.
0
0
9
1
9
1
8
2
8
2
7
3
7
3
6
4
6
4
5
5
SW2
SW3
Data rate setting switch (SW3)
This switch can set the data rate.
SW3
0
9
1
8
2
7
3
6
4
5
SW3
Data rate
0
125kbps
1
250kbps
2
500kbps
3 ... 9
PGM ( Note )
19