Network Load Considerations; Reducing Voltage Drop - Tynetec Advent xt Installation Manual

Warden call system
Hide thumbs Also See for Advent xt:
Table of Contents

Advertisement

 5. NETWORK LOAD CONSIDERATIONS
 
It is very important to take voltage drop across the system network into consideration when planning an installation. It is 
the cable resistance on the power supply wiring that gives rise to voltage drop ‐ the longer the cable run and the larger the 
current requirement, the larger the voltage drop. To perform a detailed assessment of voltage drop is complex; you need 
to know the current requirement of each device, the distance between each device and the resistance of the cable per 
metre. To estimate the worst case scenario simply take the maximum cable run and calculate the voltage drop as if all 
devices were at the end of the cable. 
 
 
Typical current requirements of devices connected to the Advent xt network are given below: 
 
24V Network Devices 
 
Standard Intercom Unit 
Remote Intercom Unit 
Ceiling Pullcord with 24V LED 
Door Entry Telephone 
Door Entry Telephone with LED on 
Combined Intercom 
Combined Intercom with LED on 
Manager/Lift Callpoint 
Network Receiver 
Status Module 
 
12V Auxiliary Devices 
 
Digital Door Panel 
 
EXAMPLE
 
The estimated voltage drop on an installation with 40 intercoms, 1 status module, 1 manager callpoint, 1 lift callpoint and 6 
network receivers on 400 metres of cable would be;  
 
 
(40 x 2mA) + (1 x 12mA) + (2 x 2mA) + (6 x 10mA) = total current 156mA (0.156A) on 24V line 
 
 
400 metres of CW1308 cable = 40
 
 
using V = I x R:    0.156A x 40
 
Devices on the 24V supply will work down to approx. 16V therefore the above drop is acceptable.  
 

REDUCING VOLTAGE DROP

 
There are several means of reducing the voltage drop; site conditions will dictate which is used; 
 
1. The best solution is to split the network into a number of short spurs rather than one long run. This has the advantage of 
smaller voltage drops per cable run and simplified fault finding. 
  
2. On large installations install a 1.0mm power pair or a CW1308 with additional spare pairs to allow "doubling‐up" on 
power conductors. Increasing the cable cross section area will reduce its resistance therefore reducing the amount of 
voltage dropped. 
 
3. Looping back the power conductors from the last intercom to the controller will form a ring circuit which will effectively 
halve the resistance. 
 
4. An auxiliary power supply can be connected to the site wiring at a suitable point to "jack‐up" the supply midway along 
the cable run. The disadvantage of this being future service engineers may not be aware of PSU's presence and the 
network will remain powered when the controller is switched off. 
 
 
 
 
 
 
 
 
 
Doc No. FM0410 issue M‐1 Page 9
 
THE RESISTANCE OF CW1308 CABLE IS 
APPROX 100 
 PER 1000 METRES
 
 
 (10
 per 100 metres) 
 = 6.24V drop on 24V line (leaving approx. 18V) 
 
Standby 
Active 
 
2mA 
10mA 
2mA 
10mA 
0mA 
10mA 
3mA 
15mA 
4.5mA 
N/A 
2mA 
70mA 
7.5mA 
N/A 
2mA 
10mA 
10mA 
10mA 
12mA 
12mA 
Standby 
Active 
 
30mA 
250mA 

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Tynetec Advent xt

Table of Contents