35. KIRK 6500 DECT ‐ REPEATER DEPLOYMENT
REPEATER POWER CONNECTION
Repeaters should be connected using 1.0 mm pair cabling, if CW1308 is being used then spare pairs can be doubled‐up
and/or looped back to form a ring circuit to reduce the voltage drop.
12V DC PSU including
Standby Battery
240V
AC
Typically the maximum distance to a repeater via CW1308 should not exceed 100 metres.
Note: connect a maximum of 6 Repeaters per 12V 2A PSU.
REPEATER DEPLOYMENT RULES
A maximum of 3 Repeaters can be configured on an IP 12 Channel Base Station; RPN = IP Address
If you have up to 3 Repeaters on an IP 12 Channel Base Station they should be numbered as:
Base Station No. "X" +64, +128 and +192. The first Base Station is No. 4, second No. 5 and so on...
A maximum of 3 Repeaters can be configured in a chain
2 Repeaters cannot have the same number
See deployment examples below; RPN = the Radio Part Number
IP Base is shaded PURPLE Repeaters are shaded GREEN Radio handover BLUE
IP Base Station
RPN 4 →
1 REPEATER DEPLOYMENT
1 Repeater connected directly:
IP Base Station
RPN 4 →
2 REPEATER DEPLOYMENT EXAMPLES
2 Repeaters connected directly:
Repeater
RPN +64
2 Repeaters connected in a chain:
IP Base Station
RPN 4 →
Doc No. FM0410 issue M‐1 Page 57
Use 1.0mm Cable
Repeater
RPN = XX
Repeater
RPN +64
IP Base Station
Repeater
RPN 4 →
RPN +128
Repeater
Repeater
RPN +64
RPN +128
4 Channel Multi Cell Repeaters
(3 per IP 12 Channel Base Station)
Repeater Power Lead Colour Code
YELLOW = 12V BLACK = 0V
Max 100m