Pa Amplifier & Smpsu Installation; Installation; Mains Supply; Termination - Tynetec Advent xt Installation Manual

Warden call system
Hide thumbs Also See for Advent xt:
Table of Contents

Advertisement

 8. PA AMPLIFIER & SMPSU INSTALLATION
 
 
 
 
 
 
 
 
 
 
 
 
12V BATTERY
 
 
 
 
 

INSTALLATION

 
The PA amplifier & SMPSU is housed in a single steel enclosure 200x500x100 mm (HxWxD) designed for wall mounting 
below the Advent xt controller.  
 

MAINS SUPPLY

 
The 240V AC mains supply should be taken from the same fused spur as the Advent xt controller. Fit the nylon strain relief 
to the socket to prevent the mains lead being inadvertently unplugged.  
 

TERMINATION

 
3 cables are provided for connection to the Advent xt termination board ‐ see table below for connections and colour 
codes. See Drg No. ZXT100 sheet 2, for larger systems with intercoms split over 2 legs see Drg No. WD0276. 
 
Terminal 
 
PA Amplifier EN 
PA Amplifier AUD 
PA Amplifier 0V 
 
RS485+ 
RS485‐ 
 
Transformer PA1 
Transformer PA2 
 
Note: the transformer PA1/PA2 connection is not polarity conscious.  
 
SMPSU & DC-DC MODULES
 
The 15V/100W switch mode power supply unit (P/No. W00585) is factory set to 13.75V DC output to supply the two 24V 
DC‐DC converters and the PA amplifier board. This voltage also charges the 12V standby battery. The SMPSU has an 
internal 20mm 3.15A mains fuse and solid state overload protection on the output. For details on changing the mains fuse 
see "27V SMPSU Module" on Page 7.  
 
The two 24V/50W DC‐DC converter modules (P/No. W00590) are factory wired to provide +/‐ 24V DC supply for the PA 
amplifier board. The DC‐DC converters have solid state overload protection and contain no user serviceable parts. 
 
PROGRAMMING
 
The All Call and Fire Tone options must be enabled in the "General Setup" programming ‐ see the Advent xt Programming 
Manual (Tynetec Doc No. FM0411). 
 
Doc No. FM0410 issue M‐1 Page 14
+24V/50W D C -D C C O N VERTER
AU D IO O U T
PA1
PA2
100V LIN E AU D IO
TRAN SFO RM ER
Colour 
Cable 
Red 
Blue 
3 Core 
Green 
Red 
2 Core 
Black 
Red 
2 Core 
Black 
 
The optional PA amplifier & SMPSU (P/No. ZXT155) allows the 
onsite manager to broadcast public address announcements 
through all intercoms simultaneously.  
 
Note; PA intercoms (P/No. ZXT206) must be fitted in all 
dwellings. One PA amplifier & SMPSU can drive approx. 80 
intercoms, for larger systems a second ZXT155 will be required 
and the site PA wiring must be split into two legs. 
 
-24V/50W D C -D C C O N VERTER
VR1 FIRE
T O N E VO L
VR2
EN
AU D IO VO L
AU D
0V
P A AM P LIFIE R
BO ARD
IS S U E "E " O N WARD
15V/100W SWITC H M O D E PSU
Connected To: 
Advent xt Termination Board EN 
Advent xt Termination Board AUD 
Advent xt Termination Board 0V 
Advent xt Termination Board RS485+ 
Advent xt Termination Board RS485‐ 
Advent xt Termination Board PA1 
Advent xt Termination Board PA2 
240V AC
M AIN S

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Tynetec Advent xt

Table of Contents