27. ETHERNET INTERFACE KIT INSTALLATION
A00382 EXPANDER BOARD
LED's 1 ‐ 6
SEE TABLE BELOW
OPTION SELECT
DIL SWITCH
SEE TABLE BELOW
LED INDICATORS
LED No.
LED1
LED2
LED3
LED4
LED5
LED6
DIL SWITCHES
DIL No.
1
2
3
4
LK1 – IP ADDRESS RESET
Short the 2 pins "LK1" to reset the default IP address.
Doc No. FM0410 issue M‐1 Page 42
Label
Function
Will be lit when the factory default IP address is set.
DEFLT ADDR SET
Will be out when a site specific IP address is set.
Should be lit to confirm the File Allocation Table
FAT MOUNTED
(FAT) has been mounted. If not lit contact Tynetec's
Customer Support.
Will be lit when the Memory Card is down to its last
CARD FULL
5% of storage capacity. Download the data and
reformat the card.
Will be lit when an Email is being sent to notify
SENDING EMAIL
system administrators that site parameters have
been changed.
‐
No Function
‐
No Function
Function
Normally OFF ‐ only switch ON when un‐mounting the Memory Card
No Function
No Function
No Function
THE RCM3365/RCM3900
RABBITCORE MODULE
IS PLUGGED ON TOP OF
THE A00382 BOARD
MEMORY CARD SLOT
RJ45 ETHERNET PORT
LK1 ‐ IP ADDRESS RESET
SEE NOTE BELOW