3.1.6

Optional Rear EN100 Ethernet Module (COM3)

The optional ethernet interface is primarily provided for support of IEC 61850 protocol. Support for IEC 870-5-103
is also provided over this interface to allow connection with Reydisp Evolution and Reydisp Manager software for
interrogation, editing and download of relay settings and other data. Ordering options are available with two RJ45
electrical connectors or with two duplex LC fibre optic connectors.
Setting name
Range
LAN Protocol
OFF, IEC60870-5-103
If this setting is set to Off, access to relay data using Reydisp Evolution and Reydisp Manager software via the
Ethernet interface is not available.
3.1.7

Connecting to the Relay via Reydisp Evolution

When Reydisp Evolution software is running all available communication ports of the PC will automatically be
detected.
On the start page tool bar open up the sub-menu File > Connect.
The 'Communication Manager' window will display all available communication ports. With the preferred port
highlighted, select the 'Properties' option and ensure the baud rate and parity match that selected in the relay
Data Comms settings. Select 'Connect' to initiate the relay-PC connection.
Via the Relay > Set Address > Address set the relay address (1-254) or alternatively search for connected
devices using the Relay > Set Address > Device Map. The relay can now be configured using the Reydisp
Evolution software. Please refer to the Reydisp Evolution Manual for further guidance.
Unrestricted © 2015 Siemens Protection Devices Limited
Default
IEC60870-5-103
Figure 3.1.7-1 PC Comm Port Selection
7SR18 Configuration Guide
Setting
Notes
Page 11 of