7SR18 Performance Specification
2.12 87HS High-Set Differential
2.12.1 Reference
Parameter
Setting
Delay setting
2.12.2 Operate and Reset Level
Attribute
I
Operate level
op
Reset level
Repeatability
Transient overreach
Variation
2.12.3 Operate and Reset Time
Attribute
t
Element basic operate time
basic
2.13 85 Inter-trip Element
2.13.1 Reference
Attribute
Delay setting
2.13.2 Operate Time
Attribute
Inter-trip base element operate time
Unrestricted Page 38 of 44
Value
1, 2 ... 30 xIn
0, 0.005... 60 s
-10 °C to +55 °C
f
- 3 Hz to f
+ 2 Hz
nom
nom
Value
0, 0.005... 60 s
Value
10 ms + 20 ms
Value
± 5 % of setting or ± 0.01In
≥ 95 % of I
OP
± 2 %
≤ 5 %
Value
> 1.1 xIn 30 ms to 50 ms (Typically 30 ms)
©2018 Siemens Protection Devices Limited