Section 3: Supervision Functions
3.1
46BC Broken Conductor
3.1.1
Reference
Parameter
NPS to PPS ratio
t
Delay setting
f
3.1.2
Operate and Reset Level
Attribute
I
Operate level
curr
Reset level
Repeatability
-10 °C to +55 °C
f
nom
Variation
harmonics to f
3.1.3
Operate and Reset Time
Attribute
t
Basic operate time 1x In to 0 A
basic
Operate time
Repeatability
f
nom
Variation
harmonics to f
Unrestricted ©2018 Siemens Protection Devices Limited
Value
20,21...100 %
0.03,04,20.0,20.1,100,101,1000,1010.....14400 s
Value
100 % I
90 % I
± 1 %
£ 5 %
± 5 %
£ 5 %
cutoff
Value
40 ms
t
+ t
f
basic
± 1 % or ± 20 ms
± 5 %
£ 5 %
cutoff
7SR18 Performance Specification
± 5 %
set
± 5 %
curr ,
, ± 1 % or ± 20 ms
Page 39 of