Siemens 7SR18 Solkor Manual page 194

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

Description
Gn 50BF-I4 Setting
Gn 50BF-1 Delay
Gn 50BF-2 Delay
17.2 VT SUPERVISION
Description
Gn 60VTS Element
Gn 60VTS Component
Gn 60VTS V
Gn 60VTS I
Gn 60VTS Vpps
Gn 60VTS Ipps Load
Gn 60VTS Ipps Fault
Gn 60VTS Delay
17.3 CT SUPERVISION
Description
Gn 60CTS-I Element
Gn 60CTS-I Setting
Gn 60CTS-I Delay
Gn 60CTS Element
Gn 60CTS Inps
Gn 60CTS Vnps
Gn 60CTS Delay
17.4 BROKEN CONDUCTOR
Description
Gn 46BC U/C Guard Setting
Gn 46BC U/C Guarded
Gn 46BC Element
Gn 46BC Setting
Gn 46BC Delay
17.5 TRIP CCT SUPERVISION
Description
Gn 74TCS-1
Gn 74TCS-1 Delay
Unrestricted
© 2016 Siemens Protection Devices Limited
Range
0.05, 0.055 ... 1.995, 2
20, 25 ... 59995, 60000
20, 25 ... 59995, 60000
Range
Disabled, Enabled
NPS, ZPS
7, 8 ... 109, 110
0.05, 0.1, 0.15, 0.2, 0.25, 0.3,
0.35, 0.4, 0.45, 0.5, 0.55, 0.6,
0.65, 0.7, 0.75, 0.8, 0.85, 0.9,
0.95, 1
1, 2 ... 109, 110
0.05, 0.1, 0.15, 0.2, 0.25, 0.3,
0.35, 0.4, 0.45, 0.5, 0.55, 0.6,
0.65, 0.7, 0.75, 0.8, 0.85, 0.9,
0.95, 1
0.05, 0.1 ... 19.95, 20
0.03, 0.04 ... 14300, 14400
Range
Disabled, Enabled
0.05, 0.1 ... 1.95, 2
0.03, 0.04 ... 14300, 14400
Disabled, Enabled
0.05, 0.1, 0.15, 0.2, 0.25, 0.3,
0.35, 0.4, 0.45, 0.5, 0.55, 0.6,
0.65, 0.7, 0.75, 0.8, 0.85, 0.9,
0.95, 1
7, 8 ... 109, 110
0.03, 0.04 ... 14300, 14400
Range
0.05, 0.1 ... 4.95, 5
No, Yes
Disabled, Enabled
20, 21 ... 99, 100
0.03, 0.04 ... 14300, 14400
Range
Disabled, Enabled
0, 0.02 ... 59.98, 60
7SR18 Solkor Settings Guide
Default
0.05xIn
60ms
120ms
Default
Disabled
NPS
7V
0.05xIn
15V
0.1xIn
10xIn
0.03s
Default
Disabled
0.05xIn
10s
Disabled
0.1xIn
10V
10s
Default
0.25xIn
No
Disabled
20%
20s
Default
Disabled
0.4s
Page 19 of 44