60Cts; Figure 5.3.2-1 Logic Diagram: Ct Supervision Function (60Cts) - Siemens 7SR18 Solkor Manual

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

7SR18 Description Of Operation
5.3.2

60CTS

Normally the presence of negative phase sequence (NPS) current in a power system is accompanied by NPS
voltage. The presence of NPS current without NPS voltage is used to indicate a current transformer failure.
The element has a setting for NPS current level 60CTS Inps and a setting for NPS voltage level 60CTS Vnps If
the negative sequence current exceeds its setting while the negative sequence voltage is below its setting for
more than 60CTS Delay then a CT failure output (60CTS Operated) is given.
Operation of the CT supervision elements can be inhibited from:
Inhibit 60CTS
A binary or virtual input.

Figure 5.3.2-1 Logic Diagram: CT Supervision Function (60CTS)

Unrestricted Page 66 of 78
©2018 Siemens Protection Devices Limited