Optional Features & Functions - Siemens SIMPRO-100 Instruction Manual

Motor protection relay
Table of Contents

Advertisement

SIMPRO-100
Interrupt:
8 A Resistive @ 250 Vac
0.75 A, L/R = 40 ms @ 24 Vdc
0.50 A, L/R = 40 ms @ 48 Vdc
0.30 A, L/R = 40 ms @ 125 Vdc
0.20 A, L/R = 40 ms @ 250 Vdc
Serial Ports
Front-Panel EIA-232 Port:300 – 19200 baud
ASCII text communication
Rear Panel
®
Modbus
EIA-485 port:
Or
ASCII EIA-232 port:
EIA-485 port isolation:
1.9.2
Optional Features &
Functions
Optional Phase Voltage Inputs
Nominal Voltage:
Four-Wire Wye or
Open-Delta
Voltages Burden:
Measuring Error:
Over-Undervoltage Elements
Setting Range:
Two Phase Overvoltage Elements
Two Phase Undervoltage Elements
One Residual Overvoltage Element
Power Factor Element
Alarm and Trip Levels
Setting Range:
Time Delays:
Measuring Error:
Reactive Power Element
Alarm and Trip Levels
Setting Range:
Time Delays:
Measuring Error:
PRIM-2400C
300 – 19200 baud
300 – 19200 baud
500 V
0 – 300 Vac
< 2 VA at 300 V
± 1%, ± 0.2V
1 – 300 Vac
0.05 – 0.99 pf
0.00 – 400.00 s
≤ 1.5%
30 – 2000 VAR, 5 A tap
6 – 400 VAR, 1 A tap
0.00 – 400.00 s
≤ 2%, Full Scale
Introduction & Specifications
Underpower Element
Alarm and Trip Levels
Setting Range:
Time Delays:
Measuring Error:
Over/Underfrequency Elements
Three Settable Levels
Setting Range:
Time Delays:
Error:
Optional Internal RTD Inputs
11 Internal RTD Inputs
Monitor Winding, Bearing, Ambient, or Other
Temperatures
PT100, Ni100, Ni120, and Cu10 RTD-Types
Supported, Field Selectable
Trip and Alarm Temperatures
Setting Range:
Error:
Open and Short Circuit Detection
Trip Voting
Thermal Model Biasing
Motor Cooling Time Learning
Optional External RTD Module
12 Remote RTD Inputs
Trip, Alarm, and Thermal Features as with
Internal RTDs
Up to 500 m Away Using Fiber-Optic Cable
Adds Remote Speed Switch Input
1
30 – 2000 W, 5 A tap
6 – 400 W, 1 A tap
0.00 – 400.00 s
≤ ± 2%, Full Scale
20.00 – 70.00 Hz
0.00 – 400.00 s
± 0.01 Hz
0° – 250°C
< ± 2°C
25