Negative Phase Sequence Overcurrent; Reference (46Dt); Operate And Reset Level (46Dt); Operate And Reset Time (46Dt) - Siemens 7SR18 Solkor Manual

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

2.2

46 Negative Phase Sequence Overcurrent

2.2.1

Reference (46DT)

Parameter
I
Setting
s
t
Delay setting
d
2.2.2

Operate and Reset Level (46DT)

Attribute
I
Operate level
op
Reset level
Repeatability
Transient overreach
(X/R £ 100)
-10 °C to +55 °C
Variation
f
nom
2.2.3

Operate and Reset Time (46DT)

Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Overshoot time
Disengaging time
2.2.4

Reference (46IT)

Parameter
char
Characteristic setting
Tm
Time Multiplier setting
I
Setting
s
I
Applied Current (for operate time)
t
Delay setting
d
t
Reset setting
res
2.2.5

Operate and Reset Level (46IT)

Attribute
I
Operate level
op
Reset level
Repeatability
-10 °C to +55 °C
Variation
f
nom
Unrestricted ©2018 Siemens Protection Devices Limited
Value
0.05, 0.06... 4.0 xIn
0.00, 0.01...20.00, 20.10... 100, 101... 1000, 1010...
10000, 10100... 14400 s
Value
100 % Is, ± 5 % or ± 1% In
³ 95 % I
± 1 %
£ -5 %
£ 5 %
£ 5 %
± 5 %
Value
Switched from 0 to 2 xIs: 40 ms, ± 10 ms
Switched from 0 to 5 xIs: 30 ms, ± 10 ms
t
+ t
basic
± 1 % or ± 10 ms
<40 ms
< 60 ms
Value
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
0.025, 0.05... 1.6, 1.7... 5, 6... 100
0.05, 0.06... 2.5 xIn
IDMTL 2 to 20 x Is
0, 0.01... 20 s
ANSI DECAYING, 0, 1... 60 s
Value
105 % Is, ± 4 % or ± 1% In
³ 95 % I
± 1 %
£ 5 %
£ 5 %
± 5 %
7SR18 Performance Specification
op
, ± 1 % or ± 10 ms
d
op
Page 19 of