Environmental Performance; General - Siemens 7SR18 Solkor Manual

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

1.6

Environmental Performance

1.6.1

General

1.6.1.1
Temperature
IEC 60068-2-1
Type
Operating range
Storage range
1.6.1.2
Humidity
IEC 60068-2-30, IEC 60068-2-78
Type
Operational test (Indoor)
Operational test (Outdoor)
1.6.1.3
Transient Overvoltage
IEC 60255-27
Type
Between all terminals and earth, or
between any two independent circuits
1.6.1.4
Insulation Class
IEC 60255-27
Type
Insulation Class when mounted in normal position of use Class I
Insulation
IEC 60255-27
Type
Between any terminal and earth
Between independent circuits
Across normally open contacts
1.6.1.5
Installation Category
IEC 60255-27
Type
Installation Category (Overvoltage Category)
1.6.1.6
Pollution Degree
IEC 60255-27
Level
Pollution Degree when mounted in its normal position of use.
Unrestricted ©2018 Siemens Protection Devices Limited
Level
-10 °C to +55 °C
-25 °C to +70 °C
Level
56 days at 40 °C and 93 % relative humidity
6 cycles at 24 h between +25 °C (97% r.h.) and +55 °C (93% r.h.)
Level
5.0 kV, 1.2/50 ms 0.5 j
Level
Level
2.5 kV AC RMS for 1 min
1.0 kV AC RMS for 1 min
Level
Category III
Pollution Degree 2
7SR18 Performance Specification
Page 13 of