7SR18 Solkor Settings Guide
Description
Gn 79 P/F Deadtime 2
Time period between the fault being cleared and the close
pulse being issued
Gn 79 P/F Prot'n Trip 3
Selects whether the third phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Gn 79 P/F Deadtime 3
Time period between the fault being cleared and the close
pulse being issued
Gn 79 P/F Prot'n Trip 4
Selects whether the fourth phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Gn 79 P/F Deadtime 4
Time period between the fault being cleared and the close
pulse being issued
Gn 79 P/F Prot'n Trip 5
Selects whether the fifth phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Gn 79 P/F HS Trips To Lockout
Selects how many High Set trips are allowed before going to
Lockout
Gn 79 P/F Delayed Trips To Lockout
Selects how many Delayed trips are allowed before going to
Lockout
18.2.2 E/F SHOTS
Description
Gn 79 E/F Prot'n Trip 1
Selects whether the first earth fault trip is Instantaneous (Fast)
or Delayed. When set to Delayed all E/F Inst Trips will be
Inhibited for this shot.
Gn 79 E/F Deadtime 1
Time period between the fault being cleared and the close
pulse being issued
Gn 79 E/F Prot'n Trip 2
Selects whether the second earth fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all E/F Inst Trips will
be Inhibited for this shot.
Gn 79 E/F Deadtime 2
Time period between the fault being cleared and the close
pulse being issued
Gn 79 E/F Prot'n Trip 3
Selects whether the third earth fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all E/F Inst Trips will
be Inhibited for this shot.
Gn 79 E/F Deadtime 3
Time period between the fault being cleared and the close
pulse being issued
Gn 79 E/F Prot'n Trip 4
Selects whether the fourth earth fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all E/F Inst Trips will
be Inhibited for this shot.
Gn 79 E/F Deadtime 4
Time period between the fault being cleared and the close
pulse being issued
Unrestricted
Page 22 of 44
Range
0, 0.1 ... 14300, 14400
Inst, Delayed
0, 0.1 ... 14300, 14400
Inst, Delayed
0, 0.1 ... 14300, 14400
Inst, Delayed
1, 2, 3, 4, 5
1, 2, 3, 4, 5
Range
Inst, Delayed
0, 0.1 ... 14300, 14400
Inst, Delayed
0, 0.1 ... 14300, 14400
Inst, Delayed
0, 0.1 ... 14300, 14400
Inst, Delayed
0, 0.1 ... 14300, 14400
© 2016 Siemens Protection Devices Limited
Default
5 s
Delayed
5 s
Delayed
5 s
Delayed
5
5
Default
Inst
5 s
Inst
5 s
Delayed
5 s
Delayed
5 s