Siemens 7SR18 Solkor Manual page 188

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

Description
Gn 51N-3 Min Operate Time
Gn 51N-3 Follower DTL
Gn 51N-3 Reset
Gn 51N-3 VTS Action
Gn 51N-3 Inrush Action
11.4 51N-4
Description
Gn 51N-4 Element
Gn 51N-4 Dir. Control
Gn 51N-4 Setting
Gn 51N-4 Char
Gn 51N-4 Time Mult (IEC/ANSI)
Gn 51N-4 Delay (DTL)
Gn 51N-4 Min Operate Time
Gn 51N-4 Follower DTL
Gn 51N-4 Reset
Gn 51N-4 VTS Action
Gn 51N-4 Inrush Action
11.5 50N-1
Description
Gn 50N-1 Element
Gn 50N-1 Dir. Control
Gn 50N-1 Setting
Gn 50N-1 Delay
Gn 50N-1 VTS Action
Gn 50N-1 Inrush Action
11.6 50N-2
Description
Gn 50N-2 Element
Gn 50N-2 Dir. Control
Gn 50N-2 Setting
Gn 50N-2 Delay
Gn 50N-2 VTS Action
Gn 50N-2 Inrush Action
11.7 50N-3
Description
Gn 50N-3 Element
Gn 50N-3 Dir. Control
Unrestricted
© 2016 Siemens Protection Devices Limited
Range
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
(IEC/ANSI) Decaying, 0 ... 59, 60
Off, Inhibit, Non-Dir
Off, Inhibit
Range
Disabled, Enabled
Non-Dir, Forward, Reverse
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
0.025, 0.03 ... 99, 100
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
(IEC/ANSI) Decaying, 0 ... 59, 60
Off, Inhibit, Non-Dir
Off, Inhibit
Range
Disabled, Enabled
Non-Dir, Forward, Reverse
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Off, Inhibit, Non-Dir
Off, Inhibit
Range
Disabled, Enabled
Non-Dir, Forward, Reverse
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Off, Inhibit, Non-Dir
Off, Inhibit
Range
Disabled, Enabled
Non-Dir, Forward, Reverse
7SR18 Solkor Settings Guide
Default
0s
0s
0s
Off
Off
Default
Disabled
Non-Dir
0.5xIn
IEC-NI
1
5s
0s
0s
0s
Off
Off
Default
Disabled
Non-Dir
0.5xIn
0s
Off
Off
Default
Disabled
Non-Dir
0.5xIn
0s
Off
Off
Default
Disabled
Non-Dir
Page 13 of 44