Shown graphically it is clear that it would be advantageous to reduce the bias slope.
0.333
0.15
0.075
To allow operation of the relay for this minimum earth fault the Bias Break Point must be set to 1.0 x I
A setting of 1 x I
, rather than 1.5 x I
N
below, Figure 7.5.2-5, shows the effect of settings applied for detecting earth faults on resistance earthed
systems. It also shows the fault point for the above example:
Where the relay is used on interconnected systems and the fault current is fed from both ends of the
feeder (double end fed) the phase comparator will generally operate.
MAGNITUDE
COMPARITOR
OPERATION
0.5
1.0
Bias Break Point Settings
Figure 7.5.2-5
Figure 7.5.2-6 to Figure 7.5.2-8 show typical values chosen for the P/F Differential, Bias Slope 1 and Bias Break
Point settings to allow an earth fault with some load biasing to be detected. Three typical relay settings used for
resistance earthed systems are shown graphically, to assist with selecting appropriate settings.
Unrestricted ©2018 Siemens Protection Devices Limited
Operate
20%
Restrain
0.666
Settings for correct Load Bias
Figure 7.5.2-4
, would be selected as this help lower the CT requirements. The Figure
N
Fault Sensitivity for Resistance Earthed Sytems
1.5
Setting of Bias Break Point for Load Bias
Restraint Current
MAGNITUDE
COMPARITOR
STABLE
Restraint Current (x I
)
N
7SR18 Applications Guide
or above.
N
Page 45 of 63