7SR18 Configuration Guide
3.1.4

Configuring Relay Data Communication

Using the keys on the relay fascia scroll down the settings menu's into the 'communications' menu and change
the settings for the communication port used on the relay. All of the below settings may not be available in all
relay types. Reydisp Evolution software uses IEC60870-5-103 protocol to communicate.
COM1 – Standard RS485 Rear Port
COM2 - USB Port
LAN – Optional Ethernet Ports
Setting name
Station Address
COM1-RS485 Protocol
COM1-RS485 Baud
Rate
COM1-RS485 Parity
COM2-USB Protocol
COM2-USB Baud Rate
COM2-USB Parity
3.1.5

Configuring Relay Protection Communication Address.

Using the keys on the relay fascia scroll down the 'Settings' menu into the 'Prot'n Comms' menu and 'Protection
Comms' sub-menu to change the 'Prot'n Address'. The sum of the addresses of both relays must add to 255. This
number must be divided between the relays typically as e.g. 1 & 254 or 2 & 253 or 3 & 252... etc.
Setting name
Protection Address
Unrestricted Page 10 of 12
Range
1 – 254 for IEC60870-5-103
0 – 247 for Modbus RTU
0 – 65520 for DNP3.0
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
75 110 150 300 600 1200
2400 4800 9600 19200
38400
NONE, ODD, EVEN
OFF, IEC60870-5-103,
DNP3.0, MODBUS-RTU,
ASCII
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
230400 460800 921600
NONE, ODD, EVEN
Range
1 – 254
Default
Notes
Address given to relay to
identify that relay from
others which may be using
0
the same path for
communication as other
relays for example in a fibre
optic hub
IEC60870-5-
COM1 is the rear mounted
103
RS485 port
19200
EVEN
IEC60870-5-
COM2 is the front USB port
103
Auto detects baud rate via
Auto detects
Connection Manager Setting
EVEN
Default
Notes
Different address could
0
signify Local or Remote
relay designation.
© 2015 Siemens Protection Devices Limited