Chapter 3 Set Up the VFD Parameters | CP2000
To enter a value, use
some cases when you are presented with a string of numbers, decimal places, dates or
times, you may need to use
change.
6. Press ENTER to save the option or changes you've made. Use ESC button to go back
up one level in the menu, or push MENU to return to the main menu.
7. Use steps 3 to 6 to make the required changes to the parameters listed below.
The following tables list the parameters that you need to set up and their recommended values.

Changes to System Parameters (00) group

Parameter
Display Text
00-20 Source of
Source of
frequency
FREQ
00-21 Source of
Source of
operation
OPER
00-22 Stop
Stop Methods
method
and
to increase or decrease the number displayed. In
and
to move the cursor's position to make a specific
Description of Parameter
The source of frequency
parameter determines which
control signal controls the
drive's frequency in AUTO
mode.
Parameter options:
0 - Keypad (not
recommended)
1 - RS-485 BACnet
2 - Analog Input (used for
hardwired I/O control)
This determines which
control signal starts or stops
the drive in AUTO mode.
Parameter options:
0 - Keypad (not
recommended)
1 - Hardwired I/O Terminals
2 - RS-485 BACnet
3 - not used
4 - not used
5 - not used
This determines what the
drive does when
commanded to stop.
Parameter options:
0 – Ramp to stop
1 – Coast to stop (preferred
for HVAC)
8
Default
Preferred
Value
Value
0
2
0
1
0
1