Chapter 4 Parameters
VFD-EL-W

Group 4 Input Function Parameters

Parameter
Keypad Potentiometer Bias
04.00
Keypad Potentiometer Bias Polarity
04.01
Keypad Potentiometer Gain
04.02
Keypad Potentiometer Negative
04.03
Bias, Reverse Motion Enable /
Disable
Start-up / Stop Method of MI
04.04
Terminals and Multi-function Input
Selection
04.05
Reserved
Start-up / Stop or Multi-function
04.06
Input Terminal (MI2)
Start-up / Stop or Multi-function
04.07
Input Terminal (MI3)
04.08
Multi-function Input Terminal (MI4)
4-10
Function
Setting
0.0–100.0%
0: Positive bias
1: Negative bias
0.1–200.0%
0: No negative bias command
1: Negative bias: REV motion enabled
Mode 1 (Pr.04.19=0)
0: MI1 start-up (keypad FWD lights) /
stop
Mode 2 (Pr.04-19=1)
0: Two-wire (1) MI1, MI2
1: Two-wire (2) MI1, MI2
2: Three-wire, MI1, MI2, MI3
0: No function
1: Multi-step speed command 1
2: Multi-step speed command 2
3: Multi-step speed command 3
5: External reset
6: Accel. / decel. inhibit
7: The 1
st
, 2
nd
acceleration or
deceleration time selection
8: JOG operation control
9: External Base Block (Refer to
Pr.08.06)
10: UP: Increase Master Frequency
11: DOWN: Decrease Master
Frequency
12: Counter trigger
13: Counter reset
14: External fault
15: PID function disabled
16: Output shutoff stop
17: Parameter lock enable
18: Operation command selection
(Pr.02.01 setting / external
terminals)
19: Operation command selection
(Pr.02.01 setting / digital keypad)
20: Operation command selection
(Pr.02.01 setting / communication)
21: Forward / reverse
22: Second frequency command
source
Default
Customer
0.0
0
100.0
0
0
-
1
2
3