Troubleshooting; Testing Sensing Element - Ametek IntelliPoint RF RML Series Installation And Operating Instructions Manual

Point level switch with manual calibration/set point
Table of Contents

Advertisement

IntelliPoint RF RML Series
Section 5: Troubleshooting
5.1

Testing Sensing Element

integral
cable
Three Terminal Probes without Shield Tab
Shield
Measured Resistance (Sensor dry and clean):
Center Wire - Shield
Center Wire - Ground
Shield - Ground
Resistance readings must be taken
using an analog ohmeter set to Rx1000 scale.
WARNING:
If IntelliPoint instrument is located in a hazardous
environment, do not open enclosure cover or make/break any
electrical connections without first disconnecting electrical
power at the source. Ensure that wiring, electrical fittings,
and conduit connections conform to electrical codes for the
specific location and hazard level.
To test the sensing element, disconnect the integral cable.
Refer to Figure 5.1.
Expect the following measurements:
Center Wire
Ground
Ohms
Ohms
Ohms
Figure 5.1
Testing Sensing Element
When tank level is known to be below the
sensor, minimum acceptable values are:
CW-G 1000 ohms.
CW-S 600 ohms.
S-G
300 ohms.
If the readings are less than the minimum
acceptable values:
1. Check to see if tank is full, or if a severe
coating is present.
2. Clean sensor and re-measure the sensor
resistances.
Note: Low resistance readings are acceptable
if the sensor is covered with a conductive
liquid. Also, low resistance readings can be
the result of material lodging in a long
mounting nozzle. Refer to Figure 2-2.
Note: A reading of zero ohms usually
indicates a metal-to-metal short circuit. Check
for contact with tank wall, mounting nozzle, or
other tank structure.