OPERATION
...........................................................................................................................................................................................................
8. Current output mode
Here you define the measured or default value which is to be outputted.
0: Default value (see above)
1: Flow rate Qm
All other values are not permitted!
30
9. Current damping
Here you define how the current output is to be damped.
Permissible values for D are 0 to 0.9 !
Output current = (1-D) x value + D x old value
10. Correction factors for current offset and current rise
The current output is adjusted in the factory through two correction factors (offset and rise).
In the event that a recalibration should really be necessary, there is a PC-based program available
which will define the new offset and rise values for you.
...........................................................................................................................................................................................................