SPECIFICATIONS
...........................................................................................................................................................................................................
Temperature input (hardware and software options)
For Ex connected loads, see approval certificate.
Terminals:
Sensor type:
38
Measuring range:
Resolution:
Current-loop connection (TERZ 94-S only!)
Terminals:
U
(min):
ext
U
(max):
ext
I
:
min
I
:
max
External load (max.):
Current output with
- minimum flow rate:
- maximum flow rate:
- Warning:
- Alarm:
Accuracy, current output:
Data for the use in hazardous areas:
Ui
=
Ii
=
Pi
=
Ci
=
Li
=
Materials used for the meter case
Spheroidal cast iron or steel, depending on the pressure class and the nominal diameter.
Aluminium is used for the threaded-end design.
...........................................................................................................................................................................................................
X9,2 (+)
X9,1 (-)
PT 1000
-20°C to 60°C
± 0.2°C
X22.1 (+)
X22,2 (-)
12 V
28 V
3.5 mA
23 mA
RLmax = (Uext - 10 V) / Imax (in Ω)
e.g. Uext = 16 V
⇒ RLmax = (16 V - 10 V) / 23 mA = 260 Ω
4 mA
20 mA
3.5 mA
23 mA
Better than 1% of the final value
28 V
110 mA
770 mW
2,2 nF
110 µF
Manual TERZ 94 · EN09a · 2017-11