6.3 AC side connection

In order to reduce the line loss of AC side (no more than 1% of Pout), Omnik suggest
that the length of AC cable from the inverter to the distribution box should not exceed
the limit below.
Model
Omniksol-15k-TL2
Omniksol-17k-TL2
Omniksol-20k-TL2
Connection Procedure
1) Strip the cable 12mm
DANGER
DANGER to life due to potential fire or electricity shock.
NEVER connect or disconnect the connectors under load.
NOTICE
Use 10-7AWG(6-10mm
connections to Omnik inverter. Use only solid wire or
stranded wire.
NOTICE
Use a residual current protective device (residual
operating current: 300mA).
Rated current
21.7A
24.6A
29.0A
12mm
2
) copper wire for all AC wiring
Length of cable
2
6 mm
35m
31m
27m
2
10 mm
59m
52m
44m