7. COMMUNICATION THAT DO NOT REQUIRE
THE SEQUENCE PROGRAM
7.2.5
When the CRL is set in the AJ71PB96F/A1SJ71PB96F the 3 services of InitiateLoadCRL, LoadCRL,
and TerminateLoadCRL.
Note
As far as possible, use the CRL obtained using the GetOD from the AJ71PB96F/A1SJ71PB96F
for the CRL to written.
If there is an error with the written CRL then a worst communication cannot be done.
In this case, use the SW0IX-PROFPE to rewrite the CRL.
InitiateLoadCRL is used to announce the initiation of the CRL setting.
When InitiateLoadCRL has ended all of the connections other than the FMA7 connection are forcefully
aborted and an FMS connection cannot be established until TerminateLoadCRL has ended.
[Parameters required by the client]
None
[Server (AJ71PB96F/A1SJ71PB96F) answer parameters]
None

CRL setting initiate (InitiateLoadCRL: Server)

Server
(A1SJ71PB96F)
InitiateLoadCRL.reques
InitiateLoadCRL.response
LoadCRL.request
LoadCRL.response
.
. .
(Repeat)
LoadCRL.request
LoadCRL.response
TerminateLoadCRL.request
TerminateLoadCRL.response
7-33