Active / Reactive Power; Power Limit; Power Vs. Frequency - Delta M42U Operation And Installation Manual

Grid-tie transformerless solar inverter
Table of Contents

Advertisement

4.3.8 Active / Reactive power

A password is required to enter Active / Reactive Power page.
This page includes two kinds of function: active power control and reactive power
control. In active power control function, there are 3 control modes:
Power Limit, Power vs. Frequency, and P(V). In reactive power control function,
there are 4 control modes: Constant cosphi, cosphi(P), Constant Q, and Q(V).
These modes will be introduced in next section.
- All function's voltage settings used by phase voltage. -
Warning:
Adj. would affect
energy production.
Password:

4.3.8.1 Power Limit

This control mode can reduce the output power to a percentage of inverter's
rated power. Users can limit the output power by set the Set Point in Power
Limit page.
Power Limit

Power vs. Frequency

P(V)
4.3.8.2 Power vs. Frequency
Inverter will reduce output power when grid frequency rises up if this mode
enabled. Users can tune the parameters in Power vs. Frequency page to
change the inverter's behavior.
Power Limit
Power vs. Frequency
P(V)
****
Figure 4-21: Active / Reactive power screens
Figure 4-22: Power Limit screens
Figure 4-23: Power vs Frequency screens
Active Power Ctrl
ENT
Reactive Power Ctrl
EXIT
Mode:
ENT
Set Point:
EXIT
Mode
ENT
F start
F recovery
Gradient
EXIT
T recovery
EXIT
65
Commissioning
ON
100%
ON
60.20 Hz
60.15 Hz
100%
300s