5.4 Active/Reactive Power Control
The parameters are set according to the requirements of the selected country.
A change to the parameter settings may result in the approval being lost.
5.4.1 P(U) Control
According to AS/NZS 4777.2:2020:
The volt–watt response mode varies the output power of the inverter in response
to the voltage at its terminal. The inverter should have the volt–watt response
mode. This mode is enabled by default.
The setting of this function can be found in the "Grid Setting" page, please refer
to previous sub-chapter for the instruction to access to this page.
Main Parameters and Operation Modes
ATTENTION
29