Active/Reactive Power Control and LVRT (Optional)
6 Active/Reactive Power Control and LVRT (Optional)
There are 2 settings for active power and 4 settings for reactive power control that can
be configured based on the requirement of the local network operator.
The parameters are set according to the requirements of the selected country.
A change to the parameter settings may result in the approval being lost.

6.1 Active Power Control

6.1.1 Power Limit

Users can reduce inverter output power by a set percentage of actual or rated
power.

6.1.2 Power vs. Frequency

According to VDE-AR-N 4105 (5.7.3.3):
At frequencies between 50.2Hz and 51.5Hz, all adjustable power generation
systems shall reduce (for frequency increase) or increase (for frequency
decrease) the active power Pm generated instantaneously (at the time of
exceeding the mains frequency 50.2Hz; freezing the value on the current level)
with a gradient of 40% of Pm per Hertz).
According to CEI 0-21 (8.5.3.2):
Within a frequency range from 50.3Hz to 51.5Hz, all adjustable production
plants equipped with static converters have to be able to reduce the currently
generated active power in case of an increase of the frequency with a variable
drop of 2% to 5% with a default value of 2.4% (with corresponds to a power
gradient of 83.3%/Hz).
User can set all necessary settings to meet the requirements from the network
operator. Please refer to actual Power vs. Frequency shown in Figure 6-1 for
the settings procedure.