6 Active/Reactive Power Control; Active Power Control; Power Vs. Voltage; Power Vs. Frequency - Delta H9E Operation And Installation Manual

Grid-tie transformerless hybrid inverter
Table of Contents

Advertisement

6 Active/Reactive Power Control
There are 2 settings for active power and 4 settings for reactive power control
that can be configured based on the requirement of the local network operator.
The parameters are set according to the requirements of the selected country.
A change to the parameter settings may result in the approval being lost.

6.1 Active Power Control

6.1.1 Power vs. Voltage

According to AS/NZS 4777.2:2020:
The volt–watt response mode varies the output power of the inverter in response
to the voltage at its terminal. The inverter should have the volt–watt response
mode. This mode is enabled by default.
curve for the volt–watt response mode

6.1.2 Power vs. Frequency

According to AS/NZS 4777.2:2020:
For response to an increase in frequency, when a disturbance results in an
increase in frequency that exceeds the continuous operation range (f
H9E inverter will reduce the power output linearly with the increase in frequency
until f
is reached. When a disturbance results in an increase in frequency that
Pmin
exceeds f
transition
grid-interactive port, linearly with the increase in frequency until f
the maximum charge rate of the energy storage is reached, or the state of charge
of the energy storage is full.
ATTENTION
Warning!Electric Shock
, Delta H9E inverter will increase the power input level through the
Active/Reactive Power Control
curve for the volt–watt response mode for
multiple mode inverters with energy storage
when charging
25
), Delta
ULCO
is reached,
Pmin