Replacement Of Surge Protection Devices (Spd) - Delta M42U Operation And Installation Manual

Grid-tie transformerless solar inverter
Table of Contents

Advertisement

Maintenance
If it's necessary to remove the insulator plate
of wiring box during Cabling or maintenance,
the insulator plate must be put back in to the
wiring box before re-install the cover, refer the
figure right.

5.2 Replacement of Surge Protection Devices (SPD)

M42/36/28U series models have the surge protection device (SPD) at both AC
and DC side as shown in Figure 5-3. Table 5-1 summarizes the specifications
of AC and DC SPD.
Description
Working voltage:
Working Current (8/20us)
Rated Current (IMAX – 8/20us)
Operating Ambient Temperature Range
Manufacturer:
WARNING !
Figure 5-3: AC and DC SPD modules
AC Module
DC Module
Sichuan Zhongguang Lightning
Protection Technologies Co., Ltd
Table 5-1: SPD Specifications
72
Insulator plate
Value
895VRMS
1175VDC
10kA
20kA
-40°C to 85°C

Advertisement

Table of Contents
loading

This manual is also suitable for:

M36uM28uM80uM60u