Figure 3-15: Guideline For Aluminum Conductor - Delta M42U Operation And Installation Manual

Grid-tie transformerless solar inverter
Table of Contents

Advertisement

Installation
Please follow the following guideline for cabling if you use aluminum cables.
Guideline for aluminum conductor :
- The oxide layer must be removed from the surface of the stripped aluminum
conductor.
- The stripped aluminum conductor is greased with Vaseline or contact grease
with comparable properties after oxide layer removed.
- Tightened with the maximum tightening torque for the modular terminal block.
- The installation location must be kept free from humidity or aggressive
atmospheres.
- It is recommend to apply to sector-shaped single-strand conductor ;
The conductor shape must match the sector-shaped connection
SE
Sector-shaped
single-strand
match the sector-shaped of the connection

Figure 3-15: Guideline for aluminum conductor

40
90°