4.6 Configuration

4.6.1 Setting the PROFIBUS station address

The PROFIBUS station address for a Navigator AWT540
transmitter can be set locally via the keypad and menus or
remotely by a master using the SET_SLAVE_ADDRESS service.
When the PROFIBUS Master sets the transmitter's station
address, the address is stored and overwrites the address
value previously held in the instrument.
IMPORTANT (NOTE) The transmitter reboots after its
PROFIBUS station address parameter is changed.
During this period it is not visible to any PROFIBUS
masters.
To change the Station Address:
1. Access the PROFIBUS Communication page – see Section
3, page 7.
Communication
PROFIBUS
Back
2. Press the
key (below the Select prompt).
The PROFIBUS page is displayed:
PROFIBUS
Slave Address
Baud Rate
Back
3. Use the
and
press the
key (below the Select prompt).
IMPORTANT (NOTE) The Baud Rate is a read-only
value.
The current Slave Address setting (for example 70) is
displayed.
10
COM/AWT540/PB–EN Rev. C | Navigator 540 | Transmitter
Select
Select
keys to scroll to Slave Address and
4. Press the
key to enter the Slave Address edit page.
5. Use the
key to move between editable numbers and
use the
and
number.
Press the
key to accept the new value and exit the
Station Address page, then press the
return to the Operator page.
IMPORTANT (NOTE) To cancel a changed value,
press and hold the
until the Cancel prompt is displayed at the bottom
right side of the page, then press the
to the previous page.

4.6.2 Integration using GSD

PROFIBUS devices differ with respect to available functionality
and parameters for each device type and manufacturer. In
order to obtain 'Plug-and-Play' configuration for PROFIBUS,
characteristic device communication features such as
manufacturer name, device name, hardware / software
versions, baud rate and the number and nature of inputs /
outputs are defined in an electronic device data sheet known
as a GSD (Generic Station Description) file.
A GSD file is readable ASCII text file that contains both general
and device-specific specifications for communication. Each of
the entries describes a feature supported by a device. By using
keywords, a configuration tool reads the device identification,
the adjustable parameters, the corresponding data type and
the permitted limit values for the configuration of the device
from the GSD. Some keywords are mandatory, for example,
Vendor_Name; others are optional, for example,
Sync_Mode_supported.
The GSD file for Navigator AWT540 transmitters specifies the
device-specific Ident No. 3402. It conforms to the PROFIBUS
standard, providing a clear and comprehensive description of
each instrument in a precisely defined format. This enables the
system configuration tool to use the information automatically
when configuring a PROFIBUS bus system.
keys to increment / decrement each
key repeatedly to
(Next) key (or press repeatedly)
key to return