ABB Navigator 540 Instruction Manual page 49

Hide thumbs Also See for Navigator 540:
Table of Contents

Advertisement

Modbus
Description
address
43060
Stream sequence - Position 7
43061
Stream sequence - Position 8
43062
Stream 1 - Enable
43063
Stream 2 - Enable
43064
Stream 3 - Enable
43065
Scheduled calibration type
43066
Scheduled calibration
frequency units
43067
Scheduled calibration
frequency daily
43068
Scheduled calibration
frequency weekly
43069
Scheduled calibration
frequency monthly
Table B.22: Multi-stream sensors – units, filter and
scheduled calibration configuration (continued)
Valid range
0 to 3
0 – End of sequence
1 – Stream 1
2 – Stream 2
3 – Stream 3
0 to 3
0 – End of sequence
1 – Stream 1
2 – Stream 2
3 – Stream 3
0 – Disabled
1 – Enabled
0 – Disabled
1 – Enabled
0 – Disabled
1 – Enabled
0 – Scheduled calibration
disabled
1 – One point calibration
(low standard)
2 – One point calibration
(high standard)
3 – Two point calibration
4 – Regeneration + two point
calibration
5 – One point air calibration
0 – Frequency off
1 – Daily
2 – Weekly
3 – Monthly
0 – Daily
1 – Two days
2 – Three days
3 – Four days
4 – Five days
5 – Six days
6 – Seven days
0 – Weekly
1 – Two weeks
2 – Three weeks
3 – Four weeks
4 – Five weeks
5 – Six weeks
6 – Seven weeks
7 – Eight weeks
0 – Monthly
1 – Two months
2 – Three months
3 – Four months
4 – Six months
5 – Twelve months
Modbus
Description
address
43070
Operator page 2 template
43071
Operator page 3 template
43072
Operator page 4 template
43073
Operator page 5 template
Table B.23: Operator page templates
Modbus
Description
address
43074
Diagnostics view
43075
Signals view
43076
Chart view
43077
Alarm view
43078
Analog output view
43079
Calibration log
43080
Alarm log
43081
Audit log
43082
Diagnostics log
Table B.24: Data view / log enables
Modbus
Description
address
43083
Date format
43084
Daylight saving – region
43085
Daylight saving – start hour for
daylight saving
43086
Daylight saving – start
occurance for daylight saving
43087
Daylight saving – start day for
daylight saving
Table B.25: Date display settings
Navigator 540 | Transmitter | COM/AWT540/PB–EN Rev. C
Valid range
0 – Off
1 – Sensor 1
2 – Sensor 2
3 – Sensor 3
4 – Sensor 4
Valid range
0 – Disabled
1 – Enabled
Valid range
0 – dd/mm/yyyy
1 – mm/dd/yyyy
2 – yyyy/mm/dd
0 – Daylight saving Off
1 – Europe
2 – USA
3 – Custom
0 to 23
1 – First
2 – Second
3 – Third
4 – Fourth
5 – Last
1 – Sunday
2 – Monday
3 – Tuesday
4 – Wednesday
5 – Thursday
6 – Friday
7 – Saturday