The ABB GSD file (Ident No. 3402) is divided into 2 sections:
— General specifications
Identification of the device, together with hardware and
software versions, baud rates supported and the possible
time intervals for monitoring times.
— DP Slave-related specifications
Information about the user parameter block for
device-specific configuration and modules containing
details of the input and output data that can be exchanged
cyclically with a PROFIBUS master.
The Navigator AWT540 GSD file (ABB_3402.gsd) is available
for download from the ABB website at: www.abb.com/fieldbus
(follow the link for PROFIBUS DP field devices).

4.6.3 Configuration from the Navigator AWT540 transmitter

PROFIBUS-related parameters are configured from the
Navigator AWT540's Communication / PROFIBUS page – see
Section 3, page 7 for access details.
PROFIBUS parameters are readable at all access levels. Write
access to secure (writable) parameters is possible only at
Advanced level. Refer to associated Operating instructions
(OI/ASO550-EN [sodium], OI/ADS550-EN [dissolved oxygen,
OI/AHM550-EN [hydrazine]) for details of Access Level page
parameters.
PROFIBUS parameters options are described in Table 4.6.
Parameter
Description
Station Address
Sets the PROFIBUS Station Address value
– see Section 4.6.1, page 10.
Baud Rate
Indicates the baud rate (in kbps) the
transmitter has locked on to (read-only
parameter).
Table 4.6: PROFIBUS parameter descriptions

4.7 Navigator AWT540-DP PROFIBUS datasheet

Item
Detail
PROFIBUS device
NAVIGATOR 500
name
(product: Navigator AWT540)
Applicable
IEC61158 (Type 3)
standards
IEC61784 (CPF3/1)
Protocols
PROFIBUS-DP (DPV0)
supported
PROFIBUS-DP extensions
(DPV1 Class 1 supported)
. DPV1 Class 2 is not supported
Note
Profile ident
Standard: 9700, 9740, 9741
support
Device specific: 3431 (4xAI, 2xTOT, 1xAO)
PROFIBUS unit
PROFIBUS DPV1 Slave
type
PROFIBUS media
RS485 (EIA-485), galvanically isolated
type
PROFIBUS bus
Wiring terminals A1/B1 (in) and A2/B2
connection
(out)
PROFIBUS slot /
PROFIBUS commands must include
index
length (in bytes) as well as slot / index.
This is so that multiple values from the
same slot (except strings) can be read /
written in a single transaction (up to the
maximum of 240 bytes). The length must
be a multiple of the 'Bytes value for the
required slot.
The index specifies the starting index for
the values returned. The starting index
plus the number of bytes must not go
beyond the end of the table. Strings must
also specify the correct length in bytes but
only single strings can be accessed in one
transaction.
Bus address
1 to 126 via local display interface
range
1 to 125 via Set_Slave_Addr service
Baud rates
9.6 kbps
supported
19.2 kbps
45.45 kbps
93.75 kbps
187.5 kbps
Master Class 1 –
Set_Prm
Slave cyclic
Chk_Cfg
services (MS0)
Set_Slave_Addr
Data_Exchange
Master Class 1 –
MS1_Read
Slave acyclic
MS1_Write
services (MS1)
Device-specific
ABB_3402.gsd
GSD file
Configuration
Local display interface
support
Table 4.7: PROFIBUS datasheet
Navigator 540 | Transmitter | COM/AWT540/PB–EN Rev. C
500 kbps
1.5 Mbps
3 Mbps
6 Mbps
12 Mbps
Get_Diag
Get_Cfg
Rd_Inp
Rd_Outp
11