266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
... 7 Commissioning

Configuration with the PC / laptop

The 266Cxx multivariable transmitters can be configured with
the aid of the following devices:
ABB Asset Vision Basic, a free-of-charge software
configurator, that can be downloaded at
www.abb.com/measurement.
Software for configuration of field devices, with the
prerequisite that it is compatible with DTM.
With the graphic user interface (DTM) all configuration
possibilities are available. The procedure for program
installation is described in the appropriate installation manual
delivered with the software.
The transmitter can be configured, read out and tested via the
program. With the aid of the integrated database a
configuration can also be executed in offline mode. Each
configuration step is subject to a plausibility check. For each
point of the program a context sensitive help can be called via
'F1'.
Immediately after receipt of the transmitter or after changing
the configuration, we recommend that back up the existing
configuration on a separate data medium under 'Save in
database'.
Operating instructions for the program 'Asset Vision Basic' are
provided in the appropriate user manual.
A RS485 interface will be needed for communication between PC
and transmitter.
The driver for this interface must support a COM port.
The communication DTM (for example 'ABB HART
Communication Servicepoint') must be set to the same
COM port as the RS485 interface.
The baud rate for configuration of the transmitter is fixed to
9600 baud and must be set to the same value inside the
communication DTM.
The communication protocol of the transmitter has to be set
to 'CONFIG/HART-RS485' with dip switch, HMI menu or
Modbus Master.
For operating with a Modbus master after configuration must
the transmitter be set back to 'OPERATE/MODBUS' with the
DTM, HMI or dip switches.
Modbus connection of 2600T
(266xxx-MV Modbus®) via USB / RS 485-converter to
PC/laptop
Figure 33: Modbus connection special for 2600T (266xxx-MV Modbus®)
Description
1
DTM and DAT200
Device DTM and Asset Vision Basic - driver and device management
tool for configuration and parameterization of intelligent field devices.
2
CommDTM
Communication DTM for the USB / RS 485 converter.
Recommendation: CodeWrights HARTCommDTM
3
DTM MV266xxx-MV Modbus
Device DTM of 2600T (266xxx-MV Modbus®)
Part of the DTM500 bundle
Driver for the configuration and parameterization of the field
device
4
USB / RS 485 converter
At the end on the MODBUS interface with 120 -resistance between
'(A)Tx/Rx+' / '(B)Tx/Rx '
5
RS 485 cable
Half-duplex wiring with (A)Tx/Rx+, (B)Tx/Rx and GND
Connect 'Tx+' und "Rx+'
Connect 'TX ' and 'Rx '
Before starting configuration via DTM, the transmitter function
must be switched from 'Operate' to 'Configuration' mode (using
the 3 buttons on the device).
Ordering number
Data sheet
9820027
DS/DTM/DAT200
Not in ABB scope of delivery
9820027
DS/DTM/DAT200
Not in ABB scope of delivery
Not in ABB scope of delivery