266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
... 8 Operation
... Interface description
16 / 32 bit–Register
Address
Parameter
32 bit
16 bit
21
401
Differential Pressure (DP)
402
22
403
Pressure (P)
404
23
405
Process Temperature
406
24
407
MV Primary Value
408
Normal Volume Flow, Mass Flow or Level
25
409
MV Secondary Value
410
Volume Flow (flow) or Volume (level)
26
411
Diagnosis Main
See Application of the Diagnosis Main and Main 2 Registers on
412
page 75.
27
414
Diagnosis Main 2
See Application of the Diagnosis Main and Main 2 Registers on
page 75.
28
415
Empty
416
41
441
Upper Calibration Point DP
442
42
443
Lower Calibration Point DP
444
43
445
Upper Calibration Point P
446
44
447
Lower Calibration Point P
448
45
450
Calibration Unit Pressure (P)
46
451
Upper Calibration Point
452
47
453
Lower Calibration Point
454
48
456
Calibration Unit T
49
458
MV Tertiary Value
459
Heat Transfer Rate (flow) or Mass (level)
51
461
Damping Time Constant DP
462
52
465
Damping Time Constant T
466
Data type
Read
Write (32 bit)
Float
04
Float
04
Float
04
Float
04
Float
04
Usign32
03, 04
Using16
03, 04
Using16
03, 04
Float
03
Float
03
Float
03
Float
03
Usign16
03
Float
03
Float
03
Usign16
03
Float
03
Float
03
Float
03
Function code
Write (16 bit)
06, 16
16
06, 16
16
06, 16
16
06, 16
16
06, 16
06, 16
06, 16
16
06, 16
16
06, 16
06, 16
06, 16
16
06, 16
16