Application Of The Diagnosis Main And Main 2 Registers - ABB 266CRH Instructions Manual

Multivariable pressure transmitter with modbus communication
Hide thumbs Also See for 266CRH:
Table of Contents

Advertisement

266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A

Application of the Diagnosis Main and Main 2 Registers

The 266CRH / 266CRT, 266CSH / 266CST has two 'Diagnosis'
(Diagnosis Main and Main 2). The Diagnosis Main register
(Address 411, 412) each containing 16 bits.
The Diagnosis Main 2 register (Address 413) containing 16 bits.
Each bit represents an error.
The registers are structured as follows:
411
= true (1)
= false (0)
Figure 3: Diagnosis Main Register (Example, 16-bit Register)
The bit position is assigned to the errors in accordance with the
'Bit' column in the table Diagnosis codes.
The following assignment applies to the example in Figure 3:
Register / Bit
Fault message
411
Process temperature out of range
Bit 3
411
Differential pressure sensor out of range
Bit 5
414
Multivariable input out of range
Bit 2
Diagnosis codes
Register
Bit
Error
Address
411
0
1
2
Fourth sensor out of range
3
Process temperature out of range
4
Static pressure sensor out of range
5
Differential pressure sensor out of range
6
7
8
Process temperature out of limits
9
Sensor temperature out of limit
10
Static pressure sensor out of limits
11
Differential pressure sensor out of limits
12
Process temperature sensor fail
13
Sensor temperature fail
14
Static pressure sensor fail
15
Differential pressure sensor fail
412
414
Diagnosis codes
Register
Bit
Address
412
0
1
2
3
4
5
6
7
M11191
8
9
10
11
12
13
14
15
414
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Error
Maximum working pressure exceeded
Input simulation active
Non-Volatile checking active
Non-Volatile storage active
Non-Volatile memory burn error
Memory failure
Electronic Interface communication error
Electronic Interface error
Non-Volatile memory burn error
Sensor memory fail
Sensor invalid
Wrong flow direction
Multivariable input invalid
Multivariable input out of range
Multivariable calculation out of range
Replace info
Electronic temperature error
Electronic diagnosis alarm
Changed operating conditions
PILD output
Configuration error
Electronic diagnosis warning
Pressure overrange
75