266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
... 8 Operation
... Interface description
Coil Register
Address
Parameter
1
Diagnosis Main[0] bit 0
2
Diagnosis Main[0] bit 1
3
Diagnosis Main[0] bit 2
4
Diagnosis Main[0] bit 3
5
Diagnosis Main[0] bit 4
6
Diagnosis Main[0] bit 5
7
Diagnosis Main[0] bit 6
8
Diagnosis Main[0] bit 7
11
Diagnosis Main[1] bit 2
12
Diagnosis Main[1] bit 3
13
Diagnosis Main[1] bit 4
14
Diagnosis Main[1] bit 5
17
Diagnosis Main[2] bit 0
18
Diagnosis Main[2] bit 1
19
Diagnosis Main[2] bit 2
20
Diagnosis Main[2] bit 3
21
Diagnosis Main[2] bit 4
24
Diagnosis Main[2] bit 7
25
Diagnosis Main[3] bit 0
26
Diagnosis Main[3] bit 1
27
Diagnosis Main[3] bit 2
31
Diagnosis Main[3] bit 6
32
Diagnosis Main[3] bit 7
33
Diagnosis Main2[0] bit 0
37
Diagnosis Main2[0] bit 4
38
Diagnosis Main2[0] bit 5
39
Diagnosis Main2[0] bit 6
40
Diagnosis Main2[0] bit 7
41
Diagnosis Main2[1] bit 0
42
Diagnosis Main2[1] bit 1
43
Diagnosis Main2[1] bit 2
44
Diagnosis Main2[1] bit 3
46
Diagnosis Main2[1] bit 5
47
Diagnosis Main2[1] bit 6
48
Diagnosis Main2[1] bit 7
Change from one to two columns
Function code
Diagnosis condition
Read
Write
01, 02
Differential pressure sensor fail
01, 02
Static pressure sensor fail
01, 02
Sensor temperature fail
01, 02
Process temperature sensor fail
01, 02
Differential Pressure Sensor out of Limits
01, 02
Static Pressure Sensor out of Limits
01, 02
Sensor temperature out of limit
01, 02
Process Temperature out of Limits
01, 02
Differential Pressure Sensor out of Range
01, 02
Static Pressure Sensor out of Range
01, 02
Process Temperature out of Range
01, 02
Fourth sensor out of Range
01, 02
Sensor invalid
01, 02
Sensor memory fail
01, 02
Non–Volatile memory burn error
01, 02
Electronic Interface error
01, 02
Electronic Interface communication error
01, 02
Memory failure
01, 02
Non–Volatile memory burn error
01, 02
Non–Volatile storage active
01, 02
Non–Volatile checking active
01, 02
Input simulation active
01, 02
Max. Working pressure exceeded
01, 02
Pressure over range
01, 02
Electronic Diagnosis warning
01, 02
Configuration error
01, 02
PILD output
01, 02
Changed operating conditions
01, 02
Electronic Diagnosis alarm
01, 02
Electronic Temperature error
01, 02
Replace info
01, 02
Multivariable Calculation out of Range
01, 02
Multivariable Input out of range
01, 02
Multivariable Input invalid
01, 02
Wrong flow direction