Wiring; Connection Of Cable - Mitsubishi MELSEC-F FX-10DM-E User Manual

Fx series display module
Table of Contents

Advertisement

FX-10DM-E DISPLAY MODULE
3.2

Wiring

3.2.1

Connection of cable

Connect the 10DM to the FX Series PLC with a cable offered as option.
Connect the L-shape connector of the cable to the RS-422 connector provided on the rear
panel of the 10DM, and connect the other connector to the programming connector of the FX
Series PLC. Because the power is supplied from the PLC to the 10DM through this cable, wir-
ing for power supply is not required.
Connection procedure
1) Connecting the cable to the 10DM
Hold the mini-DIN, 8-pin, L-shape connector of the accessory
cable (FX-20P-CAB or FX-20P-CAB0/EN) by hand. Align the
"L" mark with the direction of the notch on the connector for
PLC of the 10DM, and securely insert the connector completely.
Installation, Wiring and Maintenance 3
MINI-DIN 8pin
D-SUB 25pin
3-4
Notch
PLC or
10DM side
" L" mark on
cable side
PLC
Cable side