Quick Guide
1
1
Fault
Alarm/
number
Warning Bit
Number
60
44
69
1
79
80
29
87
47
126
250
251
Table 1.16 Warnings and Alarms
1.7 General Specifications
1.7.1 Line Power Supply 3x200–240 V AC
Adjustable frequency drive
Typical shaft output [kW]
IP20 enclosure protection
Maximum cable size in terminals (line power, compressor) [mm
Output current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Maximum input current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Maximum electrical fuses, see Table 1.9
Estimated power loss [W], Best case/typical1)
Weight enclosure protection IP20 (lbs [kg])
Efficiency [%], best case/typical
Table 1.17 3x200–240 V AC
1) At rated load conditions
26
Quick Guide
Fault text
Warning
Alarm
External Interlock
X
Pwr. Card Temp
X
X
Illegal power
X
X
section configu-
ration
Drive initialized
X
Auto DC Braking
X
Motor Rotating
X
New spare part
X
New Typecode
X
1)
Danfoss A/S © Rev. 08/2014 All rights reserved.
Trip
Cause of problem
locked
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
external interlock and reset the adjustable frequency drive
(via serial communication, digital I/O, or by pressing [Off/
Reset]).
X
The temperature sensor on the power card is either too hot
or too cold.
Internal fault. Contact the local Danfoss supplier.
All parameter settings are initialized to default settings.
The adjustable frequency drive is auto DC braking
High back emf voltage. Stop the rotor of the PM motor.
X
The power or switch mode power supply has been
exchanged. (Only on 400 V 40–125 hp [30–90 kW] units).
Contact the local Danfoss supplier.
X
The adjustable frequency drive has a new type code (only on
400 V 40–125 hp [30–90 kW] units). Contact the local Danfoss
supplier.
4 TR/VZH028
6.0
H4
2
16/6
/AWG]
20.7
-
23.0
-
182/204
17.4 [7.9]
97.3/97.0
5 TR/VZH035
6.5 TR/VZH044
7.5
10
H4
H5
16/6
16/6
25.9
33.7
-
37.1
28.3
37.0
-
41.5
229/268
369/386
17.4 [7.9]
21 [9.5]
98.5/97.1
97.2/97.1
MG18M122
Need help?
Do you have a question about the CDS803 and is the answer not in the manual?